conference-paper
Measurement and Analysis of Electrical Field around Secondary Equipment of Electronic Transformer in Equivalent GIS Due to Switch Operation
Research footprint
At a glance
- الاستشهادات
- 0
- المراجع
- 0
- Comments
- 0
Paper overview
Abstract
The radiated E-field around secondary equipment of electronic current transformer and electronic voltage transformer are measured using the developed 3-D E-field measurement system under switch on operation of an equivalent 330 kV GIS system. Based on the electrically small antenna and fiber-optic transmission technology, the designed measurement system has a wide response frequency band from 10 kHz to 400 MHz. The time-domain and frequency-domain of measured signals are analyzed respectively. Under the switch on operation with charge voltage 200 kV and load 200 pF load, the maximum E-field can reach 18.67 kV/m and the frequency domain component are mainly over megahertz.
Record transparency
Publication details
- DOI
- 10.1109/icpet55165.2022.9918438
- OpenAlex
- W4312947983
- Document type
- conference-paper
- Language
- EN
- Source
- 2022 4th International Conference on Power and Energy Technology (ICPET)
- Last metadata update
Comments
تسجيل الدخول للانضمام إلى النقاش.